Unit Specs |
Electrical |
|
General |
| Allowable Input
Voltage Range |
650-2000 VA; 85-144
Vac (full load); 75-144 (half load)
3000 VA, 120V: 90-144 Vac
3000 VA, 230V: 160-276 Vac
4500/6000 VA: 170-276 Vac |
|
Architecture |
True online,
double conversion, power isolated |
|
Diagnostics |
Full system self-test on power up |
| Input Power
Factor |
650-2000VA: .95
typical @ full load
3000-6000VA: .90 typical @ full load |
|
Networks |
Connectivity via
Ethernet & Token Ring SNMP Adapter |
| Surge Protection |
120 volt input models: Tested to
IEEE 587/ANSI C62.41 Categories A & B
230 volt models: per EN 50082-1, meets IEC 801-4, IEEE 587 |
|
Replacement Modules |
Hot-swappable external battery
packs and electronics via powerpass maintenance bypass module |
| Output Voltage
THD |
650-2000VA:
<5%, 100% non-linear load 3000-6000VA: <3%, linear load |
|
Communications |
RS-232, LAN
contacts, AS/400, Novell, 3 COM |
| Common Mode Noise Rejection |
> 60 dB |
|
UPS Bypass |
Automatic on overload or UPS
failure |
| Transverse Mode
Noise Rejection |
> 80 dB |
|
Safety |
All
Models: UL 1778, CSA-C22.2 No. 107.1; EN 50091 for all models except 3000 VA, 120V
4500/6000 VA: also EN 60950 |
| Output Regulation |
±3% |
| Output wave form |
Sine Wave |
| Load Crest Ratio |
3:1 |
|
Environmental |
Mechanical |
o |
Audible Noise |
650-2000 VA: 45 dBA @ 1 meter |
| Optional Battery
Pack Weight |
Full Pack: 52 lb
/ 23.6 kg
Half Pack: (1000-2000 EXT models only) 29.5 lb / 13.4 kg |
o |
Relative
Humididty |
5-95%
non-condensing |
| Optional Battery Pack Dimensions |
H x
W x D
5.6 x 9.9 x 15.8 in.
14.3 x 25.2 x 40.0 cm. |
o |
EMI Suppresion |
All Models: FCC Part 15, Subpart
J, Class A; Class B available on selected models <=2kVA; 230 volt input models
also CISPR Class A |
PowerPass: 650 to 1500 VA Model2 |
o |
Ambient Oper.
Temp. |
10 to 40oC
(50 to 104oF) |
| Input/Output
Freq. |
50/60Hz |
o |
Ambient Storage Temp. |
-20 to 60oC (-4 to 140oF) |
| Input/Output Current |
15 amp maximum (when nor connected
to UPS) |
o |
Packaging |
No CFCs,
rectclable |
| Surge Protection |
IEEE 587, UL 1449 |
o |
Battery |
| ESD Protection |
Withstands 25 kV |
o |
Recharge Time |
650-2000 VA: 4 hrs to 80% cap.
3000-6000 VA: 6 hrs to 90% cap. |
| Safety |
UL 1778, CSA
C22.2 |
o |
Battery Type |
Sealed,
lead-acid; maintnance free |
| *
Manufacturer's specifications subject to change without notice |