Powerware 9 Prestige

Recertified Powerware
9 Prestige Tech Notes
*

 

Model Selection guide

Model1 Input
Voltage
(Vac)
Output
Voltage
(Vac)
Frequency
(Hz)
Input
Connection2
Output
Connection
Max Output
Current
Dimensions
HxWxD (In.)
Weight
(KG/LB)
650-3000 VA Models
1000VA/700W EXT 120 120 45-65 5-15P (4) 5-15R 8.3 5.6 x 9.9 x 15.8 33.0/14.93
2000VA/1300W EXT 120 120 45-65 5-20P (4) 5-15R &
(1) 5-20R
16.0 5.6 x 9.9 x 15.8 33.0/14.93
1. EXT and 2500-6000 VA models accomodate additional battery packs
2. Includes 6-foot (2 meter) detachable line cord
3. With standard, internal battery
 

Backup Times1                                                               Top

Load3

650

800

1000

750 EXT

1000 EXT

1250 EXT

1500 EXT

2000 EXT

650-2000 VA Models (Backup Time with one additional, Full battery pack listed in Parentheses)2
200VA/140W 37 37 37 68 (216) 68 (216) 68 (216) 68 (216) 72 (228)
400VA/280W 22 22 22 32 (115) 32 (115) 32 (115) 32 (115) 34 (122)
600VA/420W 12 12 12 20 (73) 20 (73) 20 (73) 20 (73) 22 (78)
800VA/560W oo 8 8 15 (56)4 14 (56) 14 (56) 14 (56) 15 (56)
1000VA/700W oo oo 6 oo 11 (39) 11 (39) 11 (39) 12 (43)
1250VA/875W oo oo oo oo oo oo 8 (30) 9 (32)
1500VA/1050W oo oo oo oo oo oo 6 (23) 7 (25)
2000VA/1300W oo oo oo oo oo oo oo 5 (17)

2500 & 3000 VA, 230 V Models

3000 VA, 120 Model

4500 & 6000 VA Models

Load3

1
Pack5

2
Packs
3
Packs

Load3

1
Pack5
2
Packs
3
Packs

Load3

2
Packs5
3
Packs
4
Packs
5
Packs
6
Packs
400VA/280W 36.8 88 146 400VA/280W 72 150 227 1500VA/1000W 30 44 58 72 87
800VA/560W 27.6 66 110 800VA/560W 36 79 122 3000VA/2000W 14 24 32 39 47
1200VA/840W 18.4 44 73 1200VA/840W 23 53 82 4500VA/3000W 7 14 22 27 32
1600VA/1100W 13.6 33 54 1600VA/1100W 16 38 61 6000VA/4000W 5 9 14 21 25
2000VA/1400W 10.7 26 42 2000VA/1400W 12 30 48
2500VA/1750W 8.3 20 33 2500VA/1750W 8 23 37
3000VA/2100W 6.5 16 27 3000VA/2100W 6.5 17 29
1. Backup times are approximaste and listed in minutes.  Times may vary with equipment, configuration, disk access, battery
    age, temperature, etc.  The Extended Battery with charger unit (EBCU) can provide up to 8 hours of backup time.  See
    separate product literature.  Specifications subject to change without notice
2. For additional backup time charts for applications requiring up to 4 additional battery packs
3. VA at 0.7 pf.
4. 750 VA, 525W
5. One battery pack is standard; 3 battery packs maximum
6. At least two battery packs required; 6 battery packs maximum
 

Unit Specs

Electrical

General

Allowable Input Voltage Range 650-2000 VA; 85-144 Vac (full load); 75-144 (half load)
3000 VA, 120V: 90-144 Vac
3000 VA, 230V: 160-276 Vac
4500/6000 VA: 170-276 Vac
Architecture True online, double conversion, power isolated
Diagnostics Full system self-test on power up
Input Power Factor 650-2000VA: .95 typical @ full load
3000-6000VA: .90 typical @ full load
Networks Connectivity via Ethernet & Token Ring SNMP Adapter
Surge Protection 120 volt input models: Tested to IEEE 587/ANSI C62.41 Categories A & B
230 volt models: per EN 50082-1, meets IEC 801-4, IEEE 587
Replacement Modules Hot-swappable external battery packs and electronics via powerpass maintenance bypass module
Output Voltage THD 650-2000VA: <5%, 100% non-linear load 3000-6000VA: <3%, linear load Communications RS-232, LAN contacts, AS/400, Novell, 3 COM
Common Mode Noise Rejection > 60 dB UPS Bypass Automatic on overload or UPS failure
Transverse Mode Noise Rejection > 80 dB Safety All Models: UL 1778, CSA-C22.2 No. 107.1; EN 50091 for all models except 3000 VA, 120V 4500/6000 VA: also EN 60950
Output Regulation ±3%
Output wave form Sine Wave
Load Crest Ratio 3:1

Environmental

Mechanical

o Audible Noise 650-2000 VA: 45 dBA @ 1 meter
Optional Battery Pack Weight Full Pack: 52 lb / 23.6 kg
Half Pack: (1000-2000 EXT models only) 29.5 lb / 13.4 kg
o Relative Humididty 5-95% non-condensing
Optional Battery Pack Dimensions H   x    W   x   D
5.6 x 9.9 x 15.8 in.
14.3 x 25.2 x 40.0 cm.
o EMI Suppresion All Models: FCC Part 15, Subpart J, Class A; Class B available on selected models <=2kVA;  230 volt input models also CISPR Class A

PowerPass: 650 to 1500 VA Model2

o Ambient Oper. Temp. 10 to 40oC (50 to 104oF)
Input/Output Freq. 50/60Hz o Ambient Storage Temp. -20 to 60oC (-4 to 140oF)
Input/Output Current 15 amp maximum (when nor connected to UPS) o Packaging No CFCs, rectclable
Surge Protection IEEE 587, UL 1449 o

Battery

ESD Protection Withstands 25 kV o Recharge Time 650-2000 VA: 4 hrs to 80% cap.
3000-6000 VA: 6 hrs to 90% cap.
Safety UL 1778, CSA C22.2 o Battery Type Sealed, lead-acid; maintnance free
* Manufacturer's specifications subject to change without notice