Unit Specifications |
| |
Electrical Input |
| |
Voltage |
208-240VAC or 200/100, 208/120, 220/110, 240/120 |
| |
Voltage Range |
176-276 |
| |
Input Power Factor |
.98 |
| |
Frequency |
50/60 Hz (±3Hz) |
| |
Electrical Output |
| |
On Utility Voltage Regulation |
±3% of Nominal |
| |
On Battery Voltage Regulation |
±3% of Nominal |
| |
Efficiency |
88% normal operation
97% High Performance (Optional Programmable) |
| |
Frequency Regulation |
±3 Hz online; ±0.1 Hz on Battery |
| |
|
| |
LCD Display |
4 x 20 character backlit display, programmable |
| |
Language Support |
English, French, Spanish and German |
| |
Communication Slots |
2 Slots (standard) |
| |
Communication Ports |
RS232, (DB9) contact closures (std) |
| |
SNMP Capability |
SNMP / Web enabled |
| |
Emergency Power Off (EPO) |
Input for external EPO |
| |
|
| |
Topology |
True Online, Double Conversion |
| |
Diagnostics |
Full system seft-test on power up |
| |
UPS Bypass |
Automatic on overload or UPS failure |
| |
Dimensions & Weight |
See Model Selection Guide |
| |
|
| |
Safety Markings |
UL, CUL TUV |
| |
EMC Markings |
FCC & CSPR22 Class 22 |
| |
Ambient Operating/Storage Temperature |
0 to 40oC (32 to 104oF) / -20 to 40oC (60oC w/o batt) -4 to 104oF(140o F w/o batt) |
| |
Audible Noise |
<50dBA |
| |
Surge Suppression |
IEEE/ANSI C62.41 |
| |
Relative Humidity |
50 to 90%, non-condesing |
| |
REPO Port |
Meets NEC code 645-11 intent and UL Requirements |
| |
Battery |
| |
Internal Battery Type |
Sealed lead-acid; maintenance free |
| |
Battery Runtime |
See Battery Runtimes |
| |
Battery Replacement |
0 to 95% noncondensing |
| |
Recharge Time |
<4 hours standard |
| |
* Manufacturer's specifications subject to change without notice |