Unit Specifications |
| |
Electrical Input |
| |
Nominal Voltage |
120 Vac, (user-selectable for 100,110, 120 & 127 Vac) |
| |
Voltage Range |
80-144V (without using batteries) |
| |
Input Power Factor |
>.95 Typical |
| |
Frequency |
50/60 Hz, autosensing |
| |
Frequency Range |
45-65 Hz |
| |
Electrical Output |
| |
Wave Form |
Sine Wave |
| |
Frequency Regulation |
±3 Hz online, ±0.1 Hz on battery |
| |
Efficiency |
89-92%, depending on load |
| |
On Utility Voltage Regulation |
± 3% of nominal |
| |
On Battery Voltage Regulation |
± 3% of nominal |
| |
Load Crest Factor |
3 to 1 ratio |
| |
Environmental and Safety |
| |
Safety Markings |
UL, CSA, NOM |
| |
EMC Markings |
FCC Class B and VCCI Class II |
| |
Surge Suppression |
IEEE/ANSI C62.41 Cateogry B (formerly 587) |
| |
Audible Noise |
<45 dBA (on utility); <50 dBA (on battery |
| |
Ambient Operating / Storage Temperature |
0 to 40oC (32 to 104oF) /
0 to 25oC (23 to 77oF) |
| |
Relative Humididty |
5 to 90%, non-condensing |
| |
Network Transient Protector |
In and out jack for telephone/modem protection or 10Base-T network cable; UL497A tested |
| |
REPO Port |
Meets NEC code 645-11 intent and UL requirements |
| |
Communications |
| |
Serial Port |
RS-232 Communications Port standard |
| |
Communications Cable |
6-ft. comm. cable included |
| |
ConnectUPS SNMP Module (optional)2 |
SNMP card adds direct control and monitoring capabilities in SNMP-based networks |
| |
| |
RS232 Multi-Port Module (optional)2 |
Equipped with (6) comm. ports to provide serial communications to multiple devices |
| |
| |
USB Module (optional)2 |
Allows UPS to communicat with Windows 98 computers via USB port, factory installed option only |
| |
| |
General |
| |
UPS Bypass |
Automatic on overload or UPS failure |
| |
Diagnostics |
Full system self-test on power up |
| |
Topology |
True online, double-conversion |
| |
Dimensions and Weight |
See Model Selection Guide Above |
| |
Battery |
| |
Internal Battery Type |
Sealed, lead-acid; maintanance free
700/1000 VA: (2) 12V, 9 Ah
1250/2000 VA: (4) 12V, 9Ah |
| |
| |
EBM Battery Type |
PW9125 24 EBM: (8) 12V, 9 Ah
PW9125 48 EBM: (8) 12V, 9 Ah |
| |
Battery Replacement |
Hot-swappable internal and external batteries |
| |
Battery Runtime |
See Battery Run Times Above |
| |
Recharge Time |
<2 hrs. from comlete discharge to 80% capacity at nominal line conditions |
| |
Start-On-Battery |
Allows start of UPS without utility input |