Unit Specifications* |
|
Electrical Input |
|
|
1000-2200 VA |
2400-3000 VA |
5000-6000VA |
|
Nominal Voltage |
120, 208 and 230 VAC |
120, 208, 230 and 240 Vac |
200/208, 220, 230 and
240 Vac |
|
Input Voltage
ranges for user-selectable voltages |
Low
Voltage: 77-152V / High voltage: 154-288V |
160-288 |
|
Operating Frequency |
50/60Hz, Auto-sensing |
|
Frequency Range |
46-65Hz |
|
Electrical Output |
|
On Utility Voltge
Regulation |
-10%
to +6% of nominal |
|
On Battery
Voltage Regulation |
±5%
RMS |
|
Voltage Wave
Shape (on battery) |
Sine
Wave |
|
Output Protection |
Short
circuit protection |
|
Battery |
|
Battery Type |
Sealed,
lead-acid: Maintenance free |
|
Battery Run Time |
See Battery Run Time Table |
|
Battery
Replacement |
Hot-swappable
internal batteries and external batteries modules |
|
Recharge Time |
<3
hours to 90% usable capacity |
|
Start-On-Battery |
Allows
start of UPS without utility input |
|
General |
|
Electrical Power Module Replacement |
No |
Yes, hot-swap |
Yes, hot-swap |
|
Diagnotics |
Full
System self-test on power up |
|
UPS Bypass |
No Bypass |
Internal Bypass |
|
Transfer Time |
4ms
typical / 6ms max |
|
Dimensions and
weights |
See Model Selection Guide |
|
Overload (normal
operation) |
110% overload,
shutdown after 3 min., 150% overload, shutdown 10 cycles |
100-102% indefinate |
103-112% 2minutes and
>112% 12 line cycles |
|
Communications |
|
User Interface |
Front
Control Panel |
|
Audible Alarms |
For
various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS Fault |
|
Network Transient
Protector |
UL
497 A, In/Out jacks RJ45 (high voltage models network protection) & RJ11 (low voltage
models modem protection) |
No |
|
REPO Port |
Meets
NEC code 645-11 intent and UL requirements |
|
Communication Ports |
See Communications Slot |
native USB and serial port |
|
Communication Slot |
RS-232 single serial module (standard)
additional options available
|
Web/SNMPxHub card factory installed, additional options available |
|
Cable |
6-foot
communications cable included |
|
Power Management
Software |
Powerware
Software Suite CD-ROM (bundled with UPS) |
|
Environmental |
|
Safety
Certifications |
UL;
cUL; NOM; C-Tick; CE marking |
|
EMC Compliance |
FCC Part 15,
EN50091-2, Class A for 2.2kVA and RM; Class B for 1000 and 1500VA tower models |
FCC Part 15 |
EN50091-2, Class A |
|
Operating
Temperature |
0 to
40o C (32 to 104o F) |
|
Storage
Temperature |
-15
to 50o C (5 to 122o F) |
|
Relative Humidity |
0% to
95% non-condensing |
|
Lightining &
Surge Protection |
ANSI/IEEE
C62.41 (IEEE 587), IEC61000-4-5 |
|
Surge energy
rating |
High energy 6500A peak |
|
Audible Noise |
Less
than 40 dBA typical |
Less than 45 dBA typical |
|
Altitude |
3000m
(10,000 ft) without derating |
|
*
Manufacturer's specifications are subject to change without notice |