Unit Specs |
| |
Electrical Input |
| |
Voltage |
120 & 230 Vac nonminal |
| |
Online voltage range |
±20% of nominal voltage at full load |
| |
Nominal Input Frequency |
45-65 Hz, 50/60 Hz, auto sensing |
| |
Input Protection |
120 V models: circuit breaker;
230V models: AC source overcurrent protection device required |
| |
Electrical Output |
| |
Power Levels |
500-1400 VA |
| |
Online Regulation |
-10%, +6% of nominal voltage |
| |
On Battery Voltage Reg. |
±0.1 Hz of nominal frequency |
| |
Voltage wave shape |
Sine wave (during normal and battery operation) |
| |
Interconnecting cords |
2 ea. IEC-320, 10A (230V models) |
| |
Indicators and Controls |
| |
Front Panel LEDs |
Poweron, on battery, overload and battery fault |
| |
Front Panel Buttons |
On/Off and alarm silence / self-test |
| |
Communications Port |
DB9 female (UPS ships with comm. cable); USB interface optional |
| |
Power Factor |
500 VA: 0.64; 750/100 VA: 0.67; 1400 VA: 0.68 |
| |
Battery |
| |
Bettery Type |
Sealed, maintnance-free lead-acid; starved electrolyte |
| |
Battery Description |
500 VA: (1) 12V, 9 Ah
750 VA: (2) 12V, 7.2 Ah
1000 VA: (2) 12V, 9 Ah
1400 VA: (3) 12V, 9 Ah |
| |
| |
Battery Recharge |
< 3 hours to 90% capacity |
| |
Battery Runtime |
5 minutes minimum; see battery runtimes table |
| |
Start-On-Battery |
Startup with UPS batteries in absence of utility power |
| |
General |
| |
Topology |
Line-Interactive |
| |
Dimensions and weight |
See Model Selection Guide |
| |
Network Transient Protector |
In and out RJ11 jack for telephone / modem protection (120V models only) or RJ45 for 10Base-T network cable; UL497A tested |
| |
Environmental and Safety |
| |
Safety Markings |
UL, cUL and CSA; 230V models also CE and TUV |
| |
Safety Conformance |
UL 1778, CAN.CSA C22.2, No. 107.1; 230V Models also EN 50091-1-1 and IEC 60950 |
| |
EMC Markings |
FCC Class B; 230V models also CE (EN50091-2) and C-Tick |
| |
Surge Suppression |
ANSI C62.41 Category A (formerly IEEE 587) |
| |
Operating Temperature |
0 to 40oC (32 to 104oF); UL tested 25o (77oF) |
| |
Immunity |
IEC 801-2, -3, -4 |
| |
Transit / Storage Temp. |
-15 to 55oC (5 to 131oF) |
| |
Audible Noise |
<45 dBA, typical |
| |
Relative Humidity |
5-95% non-condensing |
| |
* Manufacturer's specifications are subject to change without notice |